INSTALLATION

- 11 -

Diagram 4.2

Position

Position of the flue terminal

mm

Horizontal flues
A

directly below an opening, air brick,

opening windows

300

B

above an opening, air brick, opening windows

300

C

horizontally to an opening, air brick, opening

windows

300

D

below gutter, drain/soil pipe

25

E

below eaves

25

(1)

F

below a balcony or car port

25

G

from vertical drain pipes and soil pipes

25

H

from internal/external corners

25

H

(2)

to a boundary alongside the terminal

300

I

above adjacent ground or balcony level

300

J

(2)

from surface or a boundary facing the terminal

600

Position

Position of the flue terminal

mm

L

from opening (door/window) in car port

into dwelling

1200

M

vertical from a terminal

1500

N

horizontally from a terminal

300

Vertical flues
P

from another terminal

600

Q

above roof level

300

R

from adjacent opening window

1000

S

from adjacent wall to flue

300

(1) There should be no ventilation/opening in the eaves within

300mm distance of the terminal.

(2) These dimensions comply with the building regulations,

but they may need to be increased to avoid wall staining and

nuisance from pluming depending on site conditions.