A.3.3 clearing the hardware error display, He- 111 − appendix a – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual
Page 95

HE-
111 − APPENDIX A
Rev B Mar 2013
A-9
Table A-3. Diagnostic Alarms - continued
DISPLAY
MEANING
WHAT TO DO
Err2
Error 2: RAM self-test fail
Return Controller for repair
Err3
Error 3: Watchdog fail
Return Controller for repair.
Err4
Error 4: Keyboard failure. Stuck
button or button was pressed
during power-up
Switch power off and then on, without touching any of the
controller buttons
Err5
Error 5: Faulty internal
communication
Check printed circuit board interconnections. If the fault
cannot be cleared, return the controller for repair.
Err6
Digital filter chip faulty or loose
board inside controller
Return Controller for repair
Err7
PV ID failure
Return Controller for repair
Err8
Module 1 ID failure
Faulty or loose module, or isolation problem
Err9
Module 2 ID failure
Faulty or loose module, or isolation problem
ErrA
Module 3 ID failure
Faulty or loose module, or isolation problem
dCF
DC output failure
Return Controller for repair.
O P E n
Secondary Input Missing or
Disconnected
This error may result from no power to the flow meter (check for
green power light on rear of meter or 0-5V flowmeter signal
connections), or a disconnection of the Molex connector between
feedforward sensor and the Eurotherm controller.
A.3.3 Clearing the Hardware Error Display
To clear a hardware error (HW.ER) and reset the Temperature Controller, proceed as follows:
1. Simultaneously press the Page (
) and Scroll (
) buttons on the Temperature Controller.
2. Using the Up
(▲) arrow button, change the password to “8”.
3. Simultaneously press the Page (
) and Scroll (
) buttons again and observe the Temperature
Controller display. The top line will display “8” and the bottom line will display “NO”.
4. Press the Up
(▲) arrow button to toggle the display from “NO” to “YES”.
5. Simultaneously press the Page (
) and Scroll (
) buttons to “Reset” the Temperature
Controller and clear the hardware error.