RH Compensation

Add Min Vent 30

RH set point % 65

Mist shutoff % 90

5.15.3.3 Adjusting Mist or Kool-Cel Shutoff

When the humidity level is too high, Kool-Cel or mist units are shut off to

avoid increasing the humidity level any further. This means that the fan

stage outputs that operates in timer mode stop operating whenever the

humidity level exceeds the mist shutoff limit. This limit ranges from 25%

to 100% (Off) of humidity. Set the dipswitch #5 to ON to activate this

function.

Set the function to "18.RH Compensation" from the main menu

using the navigation buttons then press the right-arrow key. Note

that this menu only appears if the relative humidity sensor has been

enabled during the installation setup (see sec. 5.14.3).

Use the navigation buttons in order

to select the "Mist Shutoff" display.

Note that this menu only appears if

dipswitch #5 is turned ON.

Use the adjustment buttons to set

the mist shutoff humidity level to the desired value.

5.15.3.4 Adjusting Heater Timer Cycle

Heaters can be activated in timer mode to compensate for a high level of

humidity. As the humidity level increases, the heaters' On-Time in-

creases proportionally to compensate for the change. Heaters reach their

MAX ON TIME

SECONDS

RELATIVE

HUMIDITY (RH)

HEATERS START

IN TIMER MODE

WITH MIN. ON TIME

0 SEC

RH SET POINT

MIN ON TIME

HEATERS REACH

MAXIMUM ON TIME

HUMIDITY COMPENSATION ON HEATERS