5.8 HEATER SETTINGS

The PP-32 operates up to eight independent heater stages. A start and

stop temperature is defined for each heating stage. The stop temperature

must be at least 0.5°F (0.3°C) greater than the start temperature for a

given heater and the start temperature cannot be greater than the set

point. The number of heater stages needed and the sensor assignment for

each stage is determined during the installation (see sec. 5.14.3 and

5.14.4). The following diagram shows the operation of an heater stage.

Start and stop temperatures of all heater stages can be set separately

for summer and winter seasons. Refer to sec. 5.2.2 to select the proper

season.

Set the function to "10. Temp. Settings" from the main menu using

the navigation buttons. The current set point is displayed.

Press the down-arrow key to select

the start or stop temperature of the

desired heater stage.

Use the adjustment buttons to set

the Start or Stop temperature to the desired value.

Proceed in similar fashion for both winter and summer seasons.

Refer to sec. 5.2.2 to select the proper season.

Set Point: 70.°F

Start/Stop Temp

Heat 4 On 78.0(S)

Heat 4 Off 79.0(S)

ON

ROOM T°

OFF

HEATER

HEATER

TURNS ON

HEATER

TURNS OFF

OPERATION OF HEATER STAGES