Pp-32 – Acme PP-32 User Manual
Page 81
81
PP-32
KOOLMASTER PP-32
REV.01
Note that the minimum ventilation curve must be turned off to
adjust its points and days. Use the down-arrow key to scroll
each point of the curve. Then the curve status then flashes on
the display. Use the adjustment buttons to turn it Off.
Set the function to "7.Min Ventilation" from the main menu then press
the right-arrow key.
Use the adjustment buttons to select the "1.On Time/ Curve" menu.
The current On-Time and the curve status are displayed.
Press the down-arrow key once. The
first day that corresponds to the first
point of the curve, flashes on the dis-
play.
Use the adjustment buttons to set the first day to the desired value.
Press the down-arrow key once again. The On-Time for the first point
is displayed.
Use the adjustment buttons to adjust the On-Time to the desired value.
Press the down-arrow key to display and adjust all other points of
the curve.
Once they are all properly set,
press the down-arrow key. The
curve state flashes on the display.
Press
to activate the curve.
NOTE: All ten points of the curve must be specified. If you don't need
ten different points, repeat the last On-Time for each unnecessary point
of the curve.
Min ventilation
Day: 1days
On Time: 15sec
Min ventilation
Curve stat On