5.7 FAN STAGES SETTINGS

The PP-32 controls up to 16 on-off fan stages. These stages operate in

a sequence to increase the level of ventilation as the room temperature

rises. Each stage can also activate relays in timer mode. The user

defines a start and stop temperature for each stage. When the room

reaches the start temperature, the stage is activated. When the room

reaches the stop temperature, the stage is deactivated. The following

diagram shows how fan stages operate.

Start temperatures are defined with respect to the set point and with

respect to each other. This means that when one of these values is

adjusted, all the consecutive values are adjusted by the same amount.

For example, if the set point is increased by 1°F, the start temperatures

for all fan stages will be increased by the same amount. The minimum

temperature difference between two start temperatures is 0.5°F.

Start and stop temperatures of all fan stages are set separately for the

summer and winter seasons. Refer to sec. 5.2.2 to select the proper

season.

The relay assignement for fan stages 1 to 4 differs depending on the

selected program. Refer to section 5.2 for further information on the

controller's programs and to section 5.14.6 to assign fan stage relays.

STAGE S+1

VENTILATION

LEVEL

ROOM T°

STAGE S

STAGE S FANS

TURN OFF

STAGE S FANS

TURN ON

STAGE S+1

FANS TURN OFF

STAGE S+1

FANS TURN ON

OPERATION OF FAN STAGES