TRANSITION BETWEEN SIDEWALL AND

TUNNEL VENTILATION MODES:

The following section describes the vent doors and curtain's behavior

when the transition between sidewall ventilation (vent doors) and tunnel

ventilation is being done. These steps are automatically performed by

the controller.

VENT DOORS TO TUNNEL :

1. Vent doors stop operating;
2. The tunnel curtain opens during the Pre-Opening time;
3. Fans of the first tunnel stage turn on;
4. The tunnel curtain automatically adjusts the static pressure level,

until it reaches

Lo Static Pressure Limit + 0.01"WC;

5. Vent doors close until the static pressure level reaches

Hi Static

Pressure Limit - 0.01"WC;

6. Steps 4 and 5 are repeated until the vent doors run for over 30

seconds without reaching

Hi Static Pressure Limit - 0.01"WC;

The house is now in tunnel mode.

TUNNEL TO VENT DOORS:

1. Tunnel fans are turned off when the temperature decreases and

reaches the first non-tunnel stage;

2. The tunnel curtain automatically adjusts the static pressure level,

until it reaches

Hi Static Pressure Limit - 0.01"WC;

3. Vent doors open until the static pressure level reaches

Lo Static

Pressure Limit + 0.01"WC;

4. Steps 2 and 3 are repeated until the tunnel curtain runs for over 30

seconds without reaching a static pressure of

Hi Static Pressure

Limit - 0.01"WC;

The house is now in sidewall ventilation mode (vent doors).