5.15.3 Humidity Control
If a humidity sensor is being used, the PP-32 has three mechanisms to
compensate for a high humidity level :
1. The humidity level can be decreased by increasing the fans' on time
during minimum ventilation cycles. Set Dipswitch #7 to ON to
activate this function;
2. Kool-Cels are shut off whenever the relative humidity is too high (this
applies to fan stage outputs that are using a timer relay). Set
Dipswitch #5 to ON to activate this function ;
3. Heaters are activated in timer mode whenever the relative humidity
is too high. Set Dipswitch #6 to ON to activate this function;
5.15.3.1 Adjusting Relative Humidity Set Point
Set the function to "18.RH Compensation" from the main menu
using the navigation buttons then press the right-arrow key. Note
that this menu only appears if the relative humidity sensor has been
enabled during the installation setup (see sec. 5.14.3).
Use the navigation buttons to
select the relative humidity set
point
(RH Set Point) display.
Use the adjustment buttons to
adjust the relative humidity set
point to the desired value.
RH Compensation
AddMinVent sec 60
RH set point % 65
Mist shutoff % Off