5.15.3 Humidity Control

If a humidity sensor is being used, the PP-32 has three mechanisms to

compensate for a high humidity level :

1. The humidity level can be decreased by increasing the fans' on time

during minimum ventilation cycles. Set Dipswitch #7 to ON to

activate this function;

2. Kool-Cels are shut off whenever the relative humidity is too high (this

applies to fan stage outputs that are using a timer relay). Set

Dipswitch #5 to ON to activate this function ;

3. Heaters are activated in timer mode whenever the relative humidity

is too high. Set Dipswitch #6 to ON to activate this function;

5.15.3.1 Adjusting Relative Humidity Set Point

Set the function to "18.RH Compensation" from the main menu

using the navigation buttons then press the right-arrow key. Note

that this menu only appears if the relative humidity sensor has been

enabled during the installation setup (see sec. 5.14.3).

Use the navigation buttons to

select the relative humidity set

point

(RH Set Point) display.

Use the adjustment buttons to

adjust the relative humidity set

point to the desired value.

RH Compensation

AddMinVent sec 60

RH set point % 65

Mist shutoff % Off