INOR PROFIPAQ-L User Manual
Page 7

7
2.3 Short form Data (complete data in chapter Specifications)
Power supply
9 – 32 VDC
Isolation
Input/Output
1500
VAC
Output
ProfIbus
PA
Profile v. 3.0 Class A&B
Operating temperature ProfIPAQ-H/-HX
-40 - +85 °C / -40 - +185 °F
ProfIPAQ-L
-20 - +70 °C / -4 - +158 °F
2.3.1 Ex Data (also see certificate and control drawings)
ProfIPAQ-H / -H/D
ProfIPAQ-HX / -HX/D
ATEX Approval
Gas
II 3G Ex nL IIC T4-T6
II 1G Ex ia IIC T4-T6
Dust
II 3GD Ex nL T 100°C
II 1G/2D Ex ia IIC T 100°C
ProfIPAQ-H/ -H/D is intended to be connected to a standard power supply (Class 2) with
maximum supply voltage to the transmitter of 30 VDC or a FNICO power supply / Segment
coupler, mounted outside the hazardous area. The data for the transmitter is:
Bus-port (connector 6 and 7)
Sensor port (1- 5)
Comm.port
Ui = Vmax :
30 VDC
Uo = Voc : 3,3 VDC
Ui = Vmax : 8,0 VDC
Ii = Imax :
no limit
Io = Isc : 0,4 mA
Ii = Imax : 450 mA
Pi = Pmax :
no limit
Po = Pt : 6,5 mW
Pi = Pmax : 0,8 W
Ci :
1 nF
Co = Ca : 500 µF
Ci :
10 nF
Li :
10 µH
Lo = La : 375 mH
Li :
1 µH
For the ambient temperature:
T6:
-40°C < Ta < +60°C / -40°F < Ta < +140°F
T5:
-40°C < Ta < +75°C / -40°F < Ta < +167°F
T4:
-40°C < Ta < +85°C / -40°F < Ta < +185°F
Dust:
-30°C < Ta < +80°C / -22°F < Ta < +176°F
ProfIPAQ-HX / -HX/D is intended to be connected to a certified intrinsic safe power
supply / Segment coupler with FISCO data, mounted outside the hazardous area. The data
for the transmitter is:
Bus-port (connector 6 and 7)
Sensor port (1- 5)
Comm.port
Ui = Vmax :
17,5 VDC
Uo = Voc : 17,5 VDC Ui = Vmax : 8,0 VDC
Ii = Imax :
380 mA
Io = Isc : 56 mA
Ii = Imax : 450 mA
Pi = Pmax :
5,32 W
Po = Pt : 244 mW
Pi = Pmax : 0,8 W
Ci :
1 nF
Co = Ca : 166 nF
Ci :
10 nF
Li :
10 µH
Lo = La : 6 mH
Li :
1 µH
For the ambient temperature:
T6:
-40°C < Ta < +45°C / -40°F < Ta < +113°F
T5:
-40°C < Ta < +60°C / -40°F < Ta < +140°F
T4:
-40°C < Ta < +85°C / -40°F < Ta < +185°F
Dust:
-30°C < Ta < +80°C / -22°F < Ta < +176°F