7.2 Termination

Bus line termination [T] consists of a series circuit of one capacitor and one film resistor

in both ends of the main bus line.
Permissible values:

R = 100 Ω ±2 %
C = 1

µF ±20 %

It is common that one of the Line terminations is included in the Segment Coupler.

Figure 31 Typical fieldbus architecture.

1 ProfiBus DP Component
2 DP / PA Segment Coupler (including 3 and 4)

3 Signal coupler

4 Power supply device

5 Junction boxes
6 PA Segment

7 Bus line termination

8 Field devices


Figure 31 shows a typical PROFIBUS architecture. The field devices with low power

consumption (e.g., pressure and temperature measuring transmitters) are powered by a
two-wire bus. Signal transmission is also performed over the bus. A non ex-installation

allows up to 32 devices per segment, depending on the power capacity of the segment

coupler. In an Ex-installation normally 10 units can be connected in each segment.

For more information concerning PROFIBUS installation, see the PROFIBUS homepage

www.profibus.com

.