Outdoor Lifestyles by Hearth & Home Technologies Inc. • Carolina • 4066-300 • Rev. X • 6/13

18

A. Mantel Projections

Figure 7.1 shows the dimensions for mantels or other com-
bustible projections above the fi replace opening.

Fireplace Structure

Noncombustible mat’l

Mantel

25 in.

(635 mm)

minimum

Ceiling or

Overhang

12 in. (305 mm)
max. combustible
mantel depth

Figure 7.1

Clearances to Mantels or other Combustibles above Appliance.

7

7

Finishing

WARNING! Risk of Fire!

Comply with all minimum clear-

ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc.).

B. Facing Material

The appliance can be covered with any noncombustible
material. Refer to Section 1.D.

It is possible for the face of the unit above the fi replace open-
ing to show signs of soot. Clean that area as frequently as
necessary to eliminate a build up of soot or permanent dis-
coloration. A noncombustible ledge (shelf) approximately 3
inches above the opening and a minimum of 3 inches out
from the face of the unit incorporated into the facing material
will help prevent the soot from going up the wall.

Note: The control box lid can be painted as desired.
Use sandpaper or other abrasive material to scuff

the surface prior to painting.