Warning – Hearth and Home Technologies Cyclone-Cust User Manual
Page 22

Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08
22
B. Disassembly of Vent Sections
To disassemble any two pieces of pipe, rotate either section 
(see Figure 8.11), so that the seams on both pipe sections 
are aligned (see Figure 8.12). They can then be carefully 
pulled apart.
Securing the Vent Sections
Vertical Sections
Vertical sections of pipe must be supported every 8 feet 
above the fi replace base. For the Cyclone, there must be 
an additional vent support (wall bracket) placed around the 
fi rst section of pipe (see Figure 8.9). The vent support or 
plumber’s strap (spaced 120º apart) may be used.
Horizontal Sections
Horizontal sections of vent must be supported every 5 feet 
with a vent support or plumber’s strap.
Figure 8.12 Align and Disassemble Vent Sections
Figure 8.11 Rotate Seams for Disassembly
Figure 8.10 Securing Horizontal Pipe Sections
Improper support may allow vent to sag or separate.
Fire Risk.
Explosion Risk.
Combustion Fume Risk.
Use vent run supports per installation 
instructions. 
Connect vent sections per installation 
instructions.
• Maintain all clearances to combustibles. 
• Do NOT allow vent to sag below 
connection point to appliance.
WARNING
Figure 8.9 Installing Support Brackets
WALL
BRACKET
WALL
STUD
8 FT.
(2.4mm)
1 IN.
MINIMUM
FIREPLACE
BASE
GLASS TUBE
SLIP SECTION
(CYCLONE-12 SLIP)
*WALL
BRACKET
3 in. Min.
DO NOT SEAL 
OR SCREW
*Note: This fi rst section of pipe must be secured to the framing to make it
rigid and allow it to support the remaining pipe sections.