beautypg.com

Vent clearances and framing, Warning – Hearth and Home Technologies Cyclone-Cust User Manual

Page 17

background image

Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08

17

A. Pipe Clearances to Combustibles

6

6

Vent Clearances and Framing

B. Wall Penetration Framing

Combustible Wall Penetration

Frame a hole in a combustible wall for an interior wall
shield fi restop, (Figure 6.2) whenever a wall is penetrated.
Use same size framing materials as those used in the wall
construction. The wall shield fi restop maintains minimum
clearances and prevents cold air infi ltration.

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.

If your local inspector requires the wall shield fi restop on
both sides, then both wall shield fi restops must have a heat
shield attached to them.

Fire Risk.

Explosion Risk.

Maintain vent clearance to combustibles as
specifi ed.

• Do not pack air space with insulation or

other materials.

Failure to keep insulation or other materials
away from vent pipe may cause fi re.

Figure 6.1 Pipe Clearances

1 in. CLEARANCE

AROUND VERTICAL

SECTIONS

3 in. TOP

CLEARANCE

1 in. SIDE AND

BOTTOM CLEARANCE

Figure 6.2 Exterior Wall Hole

Note: Slope
not required.

10 in. X 10 in.

FRAMED

OPENING

FINISHING
MATERIAL

DECORATIVE

FIRESTOP

41-3/8 in.

(+0 to -1/2 in.)

WARNING