Page 91

Liebert iCOM
®
Control
83
Liebert
®
CRV
™
Figure 73 Set alarms parameters screen - Page 1
Temp/Hum Events—This parameter enables or disables all of the temperature and humidity
events.
High Supply Temperature—This parameter sets the high temperature threshold that will trigger
an alarm on the Liebert iCOM
®
local display and any monitoring system that may be connected.
Low Supply Temperature—This parameter sets the low temperature threshold that will trigger an
alarm on the Liebert iCOM local display and any monitoring system that may be connected.
High Return Temperature—This parameter sets the threshold temperature when a return high
temperature alarm will occur.
High Return Humidity—This parameter sets the threshold humidity when a return high humidity
alarm will occur.
Low Return Humidity—This parameter sets the threshold humidity when a return low humidity
alarm will occur.
High CW Temperature—This parameter sets the threshold chilled water when a return high
chilled water temperature alarm will occur.
S201
S202
S203
S204
S205
S206
S207
S208
S209
S210
S211
PASSWORD (Actual Level 0)
????
Tem/Hum Events
Enabled
High Supply Temperature
80 °F
Low Supply Temperature
46 °F
High Return Temperature
104 °F
High Return Humidity
60 %
Low Return Humidity
15 %
High CW Temperature
°F
SET ALARMS (page 1 of 4)
UNIT 01
to change parameter
for next/previous unit
to select parameter
to confirm
then