6 remote rack sensor operation and rack view setup, Remote rack sensor operation and rack view setup – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual
Page 57

Startup
49
Liebert
®
CRV
™
Located in the Service / Rack Setup Menu of the Liebert iCOM
®
display, the sensors can be set up to
either display or control temperature, give them a rack name and draw a rack layout that can be
viewed in the User menu.
9.5.6 Remote Rack Sensor Operation and Rack View Setup
Figure 38 Rack setup screen, page 1 of 3
Once the remote rack sensors have been configured and plugged into the CAN bus network, the
control can be configured to use the sensor for either control or reference. If the sensor is set to
“Disable,” it will be ignored. The sensor node number corresponds to the DIP switch assignment of the
sensor.
Figure 39 Rack setup screen, page 2 of 3
Once a sensor has been assigned to either control or display its temperature data a virtual position
can then be assigned to the sensor. This screen configures the Rack View layout in the User menu.
This step is not required for the sensor to operate but does provide a logical position in the row for
quickly referencing affected racks near the Liebert CRV. To set up navigate using the arrow and enter
keys to highlight the Assign Sensors number range. Once the range is selected then press the enter
key to move to the rack location blocks at the bottom of the screen. The Up and Down arrow keys can
be used to select the sensor node number. For the Liebert CRV select “CRV.”
Rack Setup (page 1 of 3)
UNIT 01
S901
PASSWORD (act. Level 0)
????
S902
Remote Sensor Node 01
Control
S903
Remote Sensor Node 02
Reference
S904
Remote Sensor Node 03
Disable
S905
Remote Sensor Node 04
Control
S906
Remote Sensor Node 05
Reference
S907
Remote Sensor Node 06
Disable
S908
Remote Sensor Node 07
Control
S909
Remote Sensor Node 08
Reference
S910
Remote Sensor Node 09
Disable
S911
Remote Sensor Node 10
Control
pr e s s: f or ne x t / pr e v unit ; a nd t o s e l e c t pa r a me t e r
pr e s s: , t he n t o c ha nge pa r a m e t e r
Rack Setup (page 2 of 3)
Liebert CRV
= CRV
No Sensors
= NoS
No rack
= [blank]
Sensor Note
= 01-10
Assign Names : 01-06
07-12
13-18
19-22
02
00
00
00
00
00
01
03
04
05
06
DC01
DC03
DD02
DC05
DC07
DD04 CRV
DC09
DC11
00
00
00
00
08
07
00
CRV
00
00
00
Cold Aisle
Use the navigation keys to move from rack to rack,
Enter to select a rack, and up- or down keys to
scroll through options.
UNIT 01