Electrical Data
123
Liebert
®
CRV
™
A
PPENDIX
B - E
LECTRICAL
D
ATA
NOTICE
Risk of exceeding line-to-ground limit. Can cause equipment damage.
The electrically commutated (EC) motors included in 480V CR035 and CR040 units are
suitable for connection to power supplies with 300V or less line to ground potential. Excess
line-to-ground voltage can cause capacitor failure internal to the motors.
• Power supplies such as 480V WYE with solidly grounded neutral have 277V line to ground
and are acceptable.
• Power supplies such as 480V WYE with high resistance (or impedance) ground, 480V delta
without ground or with floating ground, 480V delta with corner ground or 480V delta with
grounded center tap will exceed the 300V line-to-ground limit.
Table 32
Liebert CRV electrical data - 60Hz (Amps)
Voltage
Air-Cooled Units
Water/Gylcol-Cooled Units
Chilled Water Units
CR035RA
CR020RA
CR035RW
CR020RW
CR040RC
460/3/60 208/3/60 460/3/60 208/3/60 460/3/60 208/3/60 460/3/60 208/3/60
460/3/60
208/3/60
Cooling with Dehumidifying, Condensate Pump, Reheat; with or without Humidifier
FLA
31.7
62.0
24.3
51.0
31.7
62.0
24.3
51.0
11.7
24.9
WSA
38.6
75.4
29.3
61.6
38.6
75.4
29.3
61.6
14.6
31.1
OPD
50
100
35
80
50
100
35
80
20
35
Cooling with Dehumidifying, Condensate Pump and Humidifier; NO Reheat
FLA
27.9
53.8
20.5
42.8
27.9
53.8
20.5
42.8
7.9
16.7
WSA
32.9
63.1
23.6
49.3
32.9
63.1
23.6
49.3
9.9
20.9
OPD
50
90
35
70
50
90
35
70
15
25
Cooling with Dehumidifying and Condensate Pump, NO Reheat, NO Humidifier
FLA
24.2
45.4
16.8
34.4
24.2
45.4
16.8
34.4
4.2
8.3
WSA
29.2
54.7
19.9
40.9
29.2
54.7
19.9
40.9
4.6
9.1
OPD
45
90
30
60
45
90
30
60
15
15
Cooling with Dehumidifying and Reheat; NO Condensate Pump, NO Humidifier
FLA
30.5
59.7
23.1
48.7
30.5
59.7
23.1
48.7
10.5
22.6
WSA
37.4
73.1
28.1
59.3
37.4
73.1
28.1
59.3
13.1
28.3
OPD
50
100
35
80
50
100
35
80
15
30
Cooling with Dehumidifying, NO Condensate Pump, NO Reheat, NO Humidifier
FLA
23.0
43.1
15.6
32.1
23.0
43.1
15.6
32.1
3.0
6.0
WSA
28.0
52.4
18.7
38.6
28.0
52.4
18.7
38.6
3.4
6.8
OPD
45
80
30
60
45
80
30
60
15
15
Table 33
Calibration of electrical components
Refrigeration Circuit
Item No.
Component
Setting
Notes
Contact
18-19
High Pressure
Transducer
Range 045 barg
Output 05V
See Liebert iCOM
®
User Manual, SL-18835
—
14
Low Pressure
Transducer
Range 017.3 barg
Output 05V
—
3
High Pressure
Switch (HP)
STOP 38.7±1 barg
START 30.0±1.5 barg
(fixed setting manual reset)
Reset
Normally
Closed
—
Clogged Filter
Differential Pressure
Switch (CF)
Setpoint range 0.54 mbar
Filter G4 = 2 mbar
Setting Ring
Normally
Closed