Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual
Page 86

Liebert iCOM
®
Control
Liebert
®
CRV
™
78
Figure 66 Wellness humidifier settings parameters screen - Page 5
Number of Starts—This parameter shows the number of starts for the unit’s humidifier.
Run Hours—This parameter shows the number of run hours for the unit’s humidifier.
Average Run Time—This parameter displays the average run time of the unit’s humidifier.
Starts per Day Best—This parameter displays the lowest number of starts in a rolling 24 hour
period.
Starts per Day Worst—This parameter displays the highest number of starts in a rolling 24 hour
period.
Number of Alarms—This parameter displays the number of high pressure alarms that have
occurred with the unit’s humidifier.
Actual Bonus—This parameter displays the actual calculation of wellness for the unit’s humidifier.
The unit will always take the value from the worst component for the next maintenance indication.
S045
S046
S047
S048
S049
S050
S051
S052
S053
S054
S055
PASSWORD
(Actual Level 0)
????
Number of Starts
14404
Run Hours
154 hrs
Average Run Time
0min
Starts per Day Best
24
Starts per Day Worst
240
Number of Alarms
0
Actual Bonus
0
WELLNESS humidifier settings (page 5 of 5)
UNIT 1
to change parameter
for next/previous unit
to select parameter
to confirm
then
Screen displayed
only if unit is
equipped with
humidifier