WA and AL Relay—
Dehumidification Enabled—This parameters selects if the compressor and / or valve will be used
to dehumidify when the humidity is above setpoint.
Auto Restart Enabled—This parameter when set to “Yes” restarts the unit after a power cycle.
When this parameter is set to “No” then the unit will not restart (Turn On) after a power cycle.
Single Unit Auto Restart—This parameter sets a time delay for the unit to restart when the Auto
Restart Enabled is set to “Yes”. The delay begins once the boot process has completed. This parameter
allows units to be staggered On to reduce the amount of simultaneous power consumption after a loss
of power.
On-Off Enabled—This parameter disables the power button on the front of the display. The default
configuration is “On”.
to change parameter
for next/previous unit
to select parameter
to confirm
then
S412
S413
S414
S415
S416
S417
S418
S419
S420
S421
S422
PASSWORD Actual Level 0)
? ???
WA and AL Relay
Direct
Dehumidification Enabled
Yes
Auto Restart Enabled
Yes
Single Unit Auto Restart
5sec
On-Off Enabled
Yes
OPTIONS SETUP (page 2 of 2)