beautypg.com

0 specifications, Table 5 parallel pod specifications, Pecifications – Emerson GXT2-PP20KRT208 User Manual

Page 33: Table 5, Parallel pod specifications, Table 6, Paralleling cable kit dimensions and weight

background image

Specifications

29

10.0 S

PECIFICATIONS

Table 5

Parallel POD specifications

Model Number

Liebert GXT2-PP20KRT208

Model Rating

20,000VA / 16,000W at 120/208 or 120/240 VAC

Dimensions, in (mm)

Unit, W x D x H in. (mm)

16.94 x 9.85 x 16.61 (430 x 250 x 422)

Shipping, W x D x H in. (mm)

23.05 x 16.74 x 19.38 (585 x 425 x 492)

Weight, lb (kg)

Unit

41.89 (19)

Shipping

48.94 (22.2)

Input AC Parameters

Nominal Operating Frequency

50 or 60 Hz

Nominal Operating Voltage

120/208 or 120/240 VAC

Input Power Connection

Hardwire Terminal Block 3W + G (L-L-N-G)

Output AC Parameters

Voltage

120/208 or 120/240 VAC

Output Connections

Hardwire Terminal Block 3W + G (L-L-N-G);

also see 3.6 - Optional Power Distribution

Frequency

50 Hz or 60 Hz, Nominal

Agency

Safety

UL / c-UL Listed as accessory for UPS

ESD

EN61000-4-2, Level 4, Criteria A

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

Conducted Immunity

EN61000-4-6 Level 3, Criteria A

EFT / Burst

EN61000-4-4, Level 4, Criteria A

Surge

EN61000-4-5, Level 3, Criteria A

ANSI C62.41 (IEEE 587) Category A (Level 3) & B (Level 1)

Transportation

ISTA 1A

Table 6

Paralleling cable kit dimensions and weight

Model Number

Liebert GXT2-20KPC-6 (1 required for each UPS)

Dimensions, in (mm)

Shipping, W x D x H in. (mm)

15.76 x 15.76 x 4.02 (400 x 400 x 120)

Weight, lb (kg)

Shipping

13.89 (6.3)