Installation

16

5.4

Add an Output Power Distribution Module—Optional

To add an optional output distribution module to the Liebert GXT2-PP20KRT208:
1. Disconnect and secure utility power from the parallel POD and completely power Off all

connected UPSs.

2. Remove the four screws securing the blank output distribution cover plate of the parallel POD.
3. Set the screws aside to attach an output distribution module to the parallel POD.
4. Snap together the color-coded, mating electrical connectors of the optional output distribution

module to the parallel POD.

5. Use the screws removed in Step 2 to attach the output distribution module to the distribution

module to the parallel POD.

!

WARNING

Risk of electric shock. Can cause equipment damage, injury or death.
Lethal voltages may exist within the UPS and parallel POD as long as the UPS is connected.
Before beginning to install the optional output distribution module, make sure the paralleling

system and all connected UPSs are completely powered off.

NOTE
The Liebert GXT2-PP20KRT208 distribution POD options are different than the distribution

PODs used with individual Liebert GXT2-10000RT208 UPSs. Each POD type has different

connectors and are not interchangeable.
If a Liebert GXT2-10000RT208 UPS that is to be connected to the parallel POD has a

distribution POD option, then the distribution POD must be removed from the UPS to connect

the parallel power cable assembly to the UPS.

PD-202

Electrical connector

snaps to connector

inside parallel POD

Screw holes to attach

to parallel POD

Screw holes to attach

to parallel POD

Optional output power

distribution module

(PD-202 shown)

Install the optional output

power distribution module

in the parallel POD