The Liebert GXT2-PP20KRT208 parallel POD allows connecting a maximum of three UPSs in paral-

lel. See the following table for the maximum output power.

7.1

Paralleling for Capacity

When two UPSs are connected to the paralleling system, the maximum output power is 20kVA. Each

UPS supplies 10kVA of output power. Redundant power is not available if either of the paralleled the

UPSs fails.

7.2

Paralleling for Capacity and Redundancy

When three UPSs are connected to the paralleling system, the maximum output power is 20kVA. plus

redundancy of one 10kVA UPS. This setup permits that the paralleling system to operate normally

even if one of the UPSs fails or runs out of battery power.
For the paralleling procedures, see 5.0 - Installation.

Table 2

Maximum output power from paralleled UPSs

Method

Number of UPSs

Maximum Output Power

Redundancy

Paralleling for Capacity

2

20kVA

Paralleling for Capacity

and Redundancy

3

20kVA

10kVA