ProSoft Technology AN-X-MOD User Manual
Page 49
AN-X-MOD (Master) Page
45
1. Connect both AN-X modules to the S908 network.
2. Autoconfigure the primary AN-X module. Create both remote I/O
and ControlLogix configuration files.
3. Upload the ControlLogix configuration to the computer and edit it.
4. Uncomment the RedundEna line and add a prefix that uniquely
identifies the AN-X.
•
Map RedundCtl to connection 0. The autoconfiguration maps it
to outputs to the connection to slot 0 but comments it out.
•
Map RedundSts to the inputs for any connection. The
autoconfiguration maps it to outputs to the connection to slot 15
but comments it out.
•
Set the ClxPrefix.
•
For each connection, add names to the DataInput and
DataOutput parameters. These names should match the names
of the internal ControlLogix arrays that will hold the data.
•
Include the LongInput option if the configuration contains 800
series modules
5. Save the modified file and upload it to the primary AN-X.
6. Autoconfigure the secondary (backup) AN-X module. Create both
remote I/O and ControlLogix configuration files.
7. Upload the ControlLogix configuration to the computer and edit it.
•
Uncomment the RedundEna line and add a prefix that uniquely
identifies the AN-X.
•
Map RedundCtl to connection 0. The autoconfiguration maps it
to outputs to the connection to slot 0 but comments it out.
•
Map RedundSts to the inputs for any connection. The
autoconfiguration maps it to outputs to the connection to slot 15
but comments it out.
•
Set the ClxPrefix. It should match the ClxPrefix for the primary
AN-X.
•
For each connection, add names to the DataInput and
DataOutput parameters. These names should match the names
of the internal ControlLogix arrays that will hold the data and
should match the names in the primary AN-X
•
Include the LongInput option if the configuration contains 800
series modules
8. Save the modified file and upload it to the secondary (backup)
AN-X.