Manual configuration – ProSoft Technology AN-X-MOD User Manual
Page 24
Page
20
AN-X-MOD (Master)
November 2011
,,,,CfgLen=2,0x0000,0x0000
,,Slot=5,Type=ACI_030_00,;Addr=d4s5,Inp=18,Out=00,AN IN 8CH UNIPOLAR
,,,,CfgLen=1,0x0001
,,Slot=6,Type=ACO_020_00,;Addr=d4s6,Inp=00,Out=08,AN OUT 4CH CURR
,,,,CfgLen=6,0x8001,0x5555,0x0000,0x0000,0x0000,0x0000
EndDrop
Drop=5,
,Rack=1,
,,Slot=2,Type=B810,;Addr=d5s2,Inp=00,Out=01,8-OUT ISO B810
,,Slot=3,Type=B804,;Addr=d5s3,Inp=00,Out=02,16-OUT B804
,,Slot=4,Type=B863,;Addr=d5s4,Inp=08,Out=00,REG 4 CH IN B863
EndDrop
When AN-X creates a configuration file, it includes comments in the file
it creates, based on the information in its module database. If you edit
the automatically generated configuration file, edit the comments as well.
See page 23 for information on how to upload the configuration from
AN-X and save it to a file.
Manual Configuration
Manual configuration is useful when the Modicon network is not
attached to the AN-X or when you need a configuration different from
the default.
Create the configuration file using a text editor or a spreadsheet such as
Excel and save it as a comma separated variable (CSV) file, with
extension csv. The file format is described on page 21.
To send the configuration to AN-X:
1. From the AN-X web interface, select Automation Network/S908 I/O
Network Configuration
.
2. Type or browse the configuration file name into the Select file: area
3. Click the Send To AN-X button to send the file to AN-X.
AN-X parses the file and shows either the current configuration if the
configuration was sent successfully or an error message if there was a
problem with the file.