ProSoft Technology 5202-DFNT-MCM4 User Manual
Page 67

Reference MCM
♦ ProLinx Gateway
Driver Manual
Modbus Master/Slave
ProSoft Technology, Inc.
Page 67 of 80
October 16, 2009
8.1.9 Preset Multiple Registers (Function Code 16)
Query
Holding registers existing within the controller can have their contents changed
by this message (a maximum of 60 registers). However, because the controller is
actively scanning, it also can alter the content of any holding register at any time.
The values are provided in binary up to the maximum capacity of the controller
(16-bit for the 184/384 and 584); unused high order bits must be set to zero.
When specified registers with contents specified.
Note: Function codes 5, 6, 15, and 16 are the only messages that will be recognized as valid for
broadcast.
Adr Func Hi
Add
Lo Add
Quantity
Byte
Cnt
Hi
Data
Lo
Data
Hi
Data
Lo
Data
Error Check
Field
11 10 00 87 00 02
04 00 0A 01 02
CRC
Response
The normal response to a function 16 query is to echo the address, function
code, starting address and number of registers to be loaded.
Adr
Func
Hi Addr
Lo Addr
Quantity
Error Check Field
11 10 00 87
00
02 56