Reference MCM

♦ ProLinx Gateway

Driver Manual

Modbus Master/Slave


ProSoft Technology, Inc.

Page 67 of 80

October 16, 2009

8.1.9 Preset Multiple Registers (Function Code 16)

Query

Holding registers existing within the controller can have their contents changed
by this message (a maximum of 60 registers). However, because the controller is
actively scanning, it also can alter the content of any holding register at any time.
The values are provided in binary up to the maximum capacity of the controller
(16-bit for the 184/384 and 584); unused high order bits must be set to zero.
When specified registers with contents specified.

Note: Function codes 5, 6, 15, and 16 are the only messages that will be recognized as valid for

broadcast.

Adr Func Hi

Add

Lo Add

Quantity

Byte

Cnt

Hi

Data

Lo

Data

Hi

Data

Lo

Data

Error Check

Field

11 10 00 87 00 02

04 00 0A 01 02

CRC

Response

The normal response to a function 16 query is to echo the address, function
code, starting address and number of registers to be loaded.

Adr

Func

Hi Addr

Lo Addr

Quantity

Error Check Field

11 10 00 87

00

02 56