7.2.13 Guard Band Timeout

0

TO

65535

A value of 1 to 65535 sets the time in milliseconds. When this period has elapsed
and no further data is received, the gateway will handle the last received data
sequence as a Modbus message to be processed.

This parameter specifies the Guard Band Timeout between packets in multi-drop
slave mode. A value of 0 uses the default time, which is roughly equivalent to the
time it would take to send 3.5 bytes at the selected baud rate. This is the delay
value specified by the Modbus RTU protocol specifications.The following Guard
Band Timeout
values will be automatically used by the gateway when Use Guard
Band
is set to Y

ES

and the Guard Band Timeout is set to the default value of zero

(0).

Baud

Guard Band Timer (ms)

110 350

150 256

300 128

600 64

1200 32

2400 16

4800 8

9600 4

19200 2

28800 2

38400 2

57600 1

115200 1

7.2.14 Request Timeout

Use this default timeout.

7.2.15 Busy Timeout

0 to 65535

This parameter specifies the number of milliseconds to wait for the DF1 Master
port to become available. If the DF1 Master port is processing a command list
request, the busy flag will be set. The flag will remain busy until the
communication transaction is complete. If the port does not become available
before the busy timeout expires, the message will be aborted. If the Master port
becomes available before this timeout expires, the request will be routed to the
Master port.