MCM Protocol Configuration

Modbus Master/Slave

Driver Manual


Page 18 of 80

ProSoft Technology, Inc.

October 16, 2009

3.1

[Modbus Port x]

The [Modbus Port x] sections of the CFG file, where x stands for 0, 1, 2, or 3, set
the Modbus Master and slave port communication parameters and define the
protocol-specific settings.

3.1.1 Enabled

Y

ES

or N

O

This flag specifies if the port on the gateway will be utilized. If the parameter is
set to N

O

, the port will not be used. If the parameter is set to Y

ES

, the port will be

used.

3.1.2 RS

Interface

0 = RS-232

1 = RS-485

2 = RS-422

This parameter is used when Ports 1, 2, and 3 are present to configure the
electrical interface for these ports.

RS Interface selections for Port 0 are done with a jumper (electrical shunt) on the
back of the gateway.

3.1.3 Type

M

ASTER

or S

LAVE

This parameter defines if the port will emulate a Master or slave device. Choose
a value of M

ASTER

to make the port function as a Modbus Master. Choose S

LAVE

to make the port function as a Modbus slave.