1 internal slave id, 2 protocol, 3 baud rate – ProSoft Technology 5202-DFNT-MCM4 User Manual
Page 48

MCM ♦ ProLinx Gateway
Modbus Port Expander (4102/5102-MBS3-MBM)
Modbus Master/Slave
Driver Manual
Page 48 of 80
ProSoft Technology, Inc.
October 16, 2009
7.1.1 Internal Slave ID
0
TO
255
This parameter defines the virtual Modbus slave address for all three slave ports
on the Port Expander. It should be set to the same value as the Slave ID of the
device attached to the gateway's Master port. Any commands received on the
slave ports, addressed to the node address entered here, will be passed by the
gateway to the slave attached to the gateway's Master port. Any response
received from the slave will be passed back through the gateway's slave port on
which it was received.
7.1.2 Protocol
RTU
ASCII
This parameter specifies the Modbus protocol version to be used on the port.
Valid Protocols are RTU and ASCII.
7.1.3 Baud
Rate
This is the baud rate to be used on the Master port. It must match the baud rate
setting used by the slave that will be connected to this Master port.
To maximize the port multiplexing capability of the gateway, it is recommended, if
possible, that you set the baud rate on the Master port and on the attached slave
as high as the slave can accommodate, up to 38,400; then set the baud rate for
the gateway slave ports and remote Master networks to a lower setting. This will
help prevent multiple Masters from overloading the response capability of the
single slave and the gateway.
Enter the baud rate as a value, shown in this list.
Baud Rate
Parameter Value
110
110
150
150
300
300
600
600
1200
12
OR
1200
2400
24
OR
2400
4800
48
OR
4800
9600
96
OR
9600
14,400
14,
114
OR
14400
19,200
19,
192
OR
19200
28,800
28,
288
OR
28800
38,400
38,
384
OR
38400
57,600
57
OR
576
115,200
115
OR
1152