MCM ♦ ProLinx Gateway
MCM Protocol Configuration
Modbus Master/Slave
Driver Manual
Page 20 of 80
ProSoft Technology, Inc.
October 16, 2009
3.1.6 Float
Offset
0
TO
3998
This parameter defines the starting register for floating-point data in the internal
gateway database. This parameter is used only if the Float Flag is set to Y
ES
.
For example, if the Float Offset value is set to 3000 and the Float Start parameter
is set to 7000, the data returned as floating-point data for register 47001 (or
407001) will actually come from internal gateway registers 3000 and 3001. If the
requested address was 47002 (407002), the data will be returned from internal
registers 3002 and 3003. If the requested address was 47101 (407101), the data
will be returned from internal registers 3200 and 3201; and so on.
3.1.7 Protocol
RTU
ASCII
This parameter specifies the Modbus protocol version to be used on the port.
Valid Protocols are RTU and ASCII.
3.1.8 Baud
Rate
This is the baud rate to be used on the port. Enter the baud rate as a value.
Baud Rate
Parameter Value
110
110
150
150
300
300
600
600
1200
12
OR
1200
2400
24
OR
2400
4800
48
OR
4800
9600
96
OR
9600
14,400
14,
114
OR
14400
19,200
19,
192
OR
19200
28,800
28,
288
OR
28800
38,400
38,
384
OR
38400
57,600
57
OR
576
115,200
115
OR
1152
Note: On all ProLinx gateways, data from the application port on the main board, serial Port 0, is
not buffered. Packets go directly to and from the serial chipset to the processor. This has the
potential to cause the serial communications to become erratic at baud rates above 38,400 baud.
ProLinx gateways with 4 serial ports have a separate serial interface board for serial Ports 1, 2,
and 3. These serial ports are buffered, and can handle communications up to 115,200 baud.