ProSoft Technology 5202-DFNT-MCM4 User Manual
Page 53
Modbus Port Expander (4102/5102-MBS3-MBM)
MCM ♦ ProLinx Gateway
Driver Manual
Modbus Master/Slave
ProSoft Technology, Inc.
Page 53 of 80
October 16, 2009
7.2.6 Data
Bits
7
or 8
This parameter sets the number of data bits for each word used by the protocol.
All devices communicating through this port must use the same number of data
bits.
7.2.7 Stop
Bits
1 or 2
Stop bits signal the end of a character in the data stream. For most applications,
use one stop bit. For slower devices that require more time to re-synchronize,
use two stop bits.
All devices communicating through this port must use the same number of stop
bits.
7.2.8 RTS
On
0 to 65535 milliseconds
This parameter sets the number of milliseconds to delay after Ready To Send
(RTS) is asserted before data will be transmitted.
7.2.9 RTS
Off
0 to 65535 milliseconds
This parameter sets the number of milliseconds to delay after the last byte of
data is sent before the RTS modem signal will be set low.
7.2.10 Minimum Response Delay
0
TO
65535
This parameter is used only when the port is configured as a slave. It sets the
number of milliseconds to wait before responding to a command received on the
port from a remote Master. This delay is sometimes required to accommodate
slower Master devices.