Functional Overview

MCM ♦ ProLinx Gateway

Driver Manual

Modbus Master/Slave


ProSoft Technology, Inc.

Page 13 of 80

October 16, 2009

2.3

Modbus Master/Slave Port Specifications

Type Specifications

General Parameters

Internal Database

Up to 4000 registers (words) available.

Communication parameters

Port 0: Baud Rate: 110 to 115K baud possible

110 to 38.4K baud recommended for all applications.
Higher baud rates are recommended only for use
with very slow Modbus polling rates (e.g. 1command
or less per second)

Port 1, 2, 3: Baud Rate: 110 to 115K baud

Stop Bits: 1 or 2

Data Size: 5 to 8 bits

Parity: None, Even, Odd, Mark, Space

RTS Timing delays: 0 to 65535 milliseconds

Modbus Modes

RTU mode (binary) with CRC-16

ASCII mode with LRC error checking

Floating Point Data

Floating point data movement supported, including
configurable support for Enron implementation

Modbus Function Codes

1: Read Coil Status

2: Read Input Status

3: Read Holding Registers

4: Read Input Registers

5: Force (Write) Single Coil

6: Preset (Write) Single Register

15: Force(Write) Multiple Coils

16: Force (Write) Multiple Register

Modbus Master

Command List

Up to 100 command per Master port, each fully
configurable for function, slave address, register
to/from addressing and word/bit count

Status Data

Error codes available on an individual command
basis. In addition, a slave status list is maintained
per active Modbus Master port.

Polling of command list

Configurable polling of command list, including
continuous and on change of data

Modbus Slave

Node address

1 to 247 (software selectable)

Status Data

Error codes, counters and port status available per
configured slave port starting at memory register
4400.