beautypg.com

ProSoft Technology 5202-DFNT-MCM4 User Manual

Page 30

background image

MCM ♦ ProLinx Gateway

MCM Protocol Configuration

Modbus Master/Slave

Driver Manual


Page 30 of 80

ProSoft Technology, Inc.

October 16, 2009

These swap operations affect 4-byte (or 2-word) groups of data. Therefore, data
swapping using these Swap Codes should be done only when using an even
number of words, such as when 32-bit integer or floating-point data is involved.

3.2.6 Slave

Address

0 - Broadcast to all nodes

1 to 255

Use this parameter to specify the slave address of a remote Modbus Serial
device through a Modbus Ethernet to Serial converter.

Note: Use the Node IP Address parameter to address commands to a remote Modbus TCP/IP
device.
Note: Most Modbus devices accept an address in the range of only 1 to 247, so check with slave

device manufacturer to see if a particular slave can use addresses 248 to 255.
If the value is set to zero, the command will be a broadcast message on the network. The Modbus
protocol permits broadcast commands for write operations. Do not use node address 0 for read

operations.

3.2.7 Modbus

Function

1, 2, 3, 4, 5, 6, 15, or 16

This parameter specifies the Modbus Function Code to be executed by the
command. These function codes are defined in the Modbus protocol. The
following table lists the purpose of each function supported by the module. More
information on the protocol is available from www.modbus.org.

Modbus Function Code

Description

1

Read Coil Status

2

Read Input Status

3

Read Holding Registers

4

Read Input Registers

5

Force (Write) Single Coil

6

Preset (Write) Single Register

15

Force Multiple Coils

16

Preset Multiple Registers