Func type, Data type – ProSoft Technology MVI56E-SIE User Manual
Page 65

MVI56E-SIE ♦ ControlLogix Platform
Configuring the MVI56E-SIE Module
Client Communication Module
User Manual
ProSoft Technology, Inc.
Page 65 of 168
September 6, 2012
Func Type
This parameter can either be Read or Write.
Data Type
This parameter can be: BOOL, BYTE, DINT, REAL, INT, TIME, or COUNT.
Address Type
This parameter can be: INPUT, OUTPUT, FLAG, TIMER, COUNTER or DB
(Data Block).
DB Number
This parameter specifies the Data Block number to be used with the command.
DB Number is only used when the Address Type is set to DB.
Address
For Read or Write operations using the INT, DINT, REAL or BYTE Data Types,
the address is a byte address.
For Read or Write operations using the BOOL Data Type, the address is a bit
address.
Please note below:
S7-300/S7-1200 Processor:
Byte Address in Data Block:
DB1.DBB1 DB1.DBB3
2#0000_0110 2#0000_0000 2#0110_0001 2#0011_0110 2#1100_0110
DB1.DBB0
DB1.DBB2
DB1.DBB4
Word Address in Data Block:
DB1.DBW1 DB1.DBW3
2#0000_0110 2#0000_0000 2#0110_0001 2#0011_0110 2#1100_0110
DB1.DBW0 DB1.DBW2