3 client command errors – ProSoft Technology MVI56E-SIE User Manual
Page 130

Diagnostics and Troubleshooting
MVI56E-SIE ♦ ControlLogix Platform
User Manual
Client Communication Module
Page 130 of 168
ProSoft Technology, Inc.
September 6, 2012
4.3.3 Client Command Errors
There are several different ways to view Client Command Errors.
In the SIE.STATUS.CmdErrorList controller tag array
On the Client status data screens in the ProSoft Configuration Builder
Diagnostics
At a module database location specified by the configuration's SIE Client x
Command Error Pointer, if the Command Error Pointer is enabled. This
means that the first register refers to command 1 and so on.
Word Offset
Description
0
Command 0 Error
1
Command 1 Error
2
Command 2 Error
3
Command 3 Error
…
….
…
…
15
Command 15 Error
16
Command 16 Error
For every command that has an error, the module automatically sets the poll
delay parameter to 30 seconds. This instructs the module to wait 30 seconds
until it attempts to issue the command again.
As the commands in the Client Command Last are polled and executed, an error
value is maintained in the module for each command. This error list can be
transferred to the processor.