2 functional specifications, 3 hardware specifications – ProSoft Technology MVI56E-SIE User Manual
Page 135

MVI56E-SIE ♦ ControlLogix Platform
Reference
Client Communication Module
User Manual
ProSoft Technology, Inc.
Page 135 of 168
September 6, 2012
5.1.2 Functional Specifications
Siemens Industrial Ethernet data types overlap in the module's memory
database, so the same data can be conveniently read or written as bit-level or
register-level data.
Configurable floating-point data movement is supported
Configurable parameters for the Client including a minimum response delay
of 0 to 65535 ms
Supports up to 20 Clients with up to 16 commands for each Client
Error codes, counters, and module status available from module memory
through the Clients, or through the ladder logic and controller tags in
RSLogix 5000
5.1.3 Hardware Specifications
Specification
Description
Dimensions
Standard 1756 ControlLogix
®
single-slot module
Backplane current load
800 mA @ 5 Vdc
3 mA @ 24 Vdc
Operating temperature
0°C to 60°C (32°F to 140°F)
Storage temperature
-40°C to 85°C (-40°F to 185°F)
Shock
30 g operational
50 g non-operational
Vibration
5 g from 10 Hz to 150 Hz
Relative humidity
5% to 95% (with no condensation)
LED indicators
Battery Status (ERR)
Application Status (APP)
Module Status (OK)
4-character, scrolling, alphanumeric
LED display
Shows module, version, IP, application port setting, port
status, and error information
Ethernet port
10/100 Base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection
Cable
5-foot Ethernet straight-through cable (shipped with unit)