Amprobe – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual
Page 64

AMPROBE
DMIII MULTITEST
EN-62
7.7.2. "METER" mode
By selecting this function the instrument selects automatically the METER mode 
corresponding to one of the screens below according to the settings made as per 
paragraph 7.1. 
 
27.09.00 17:35:12
27.09.00 17:35:12
27.09.00 17:35:12
ENERGY
SINGLE PHASE
Ea1 = 0.000 kWh
Erc1 = 0.000 kVARh
Eri1 = 0.000 kVARh
Es1 = 0.000 kVAh
P1 = 36.38 kW
Q1 = 6.375 kVAR
S1 = 36.94 kVA
Meas Time: 00:00:00
ENERGY
THREE PHASE
Eat = 0.000 kWh
Erct = 0.000 kVARh
Erit = 0.000 kVARh
Est = 0.000 kVAh
Pt = 36.38 kW
Qt = 6.375 kVAR
St = 36.94 kVA
Meas Time: 00:00:00
ENERGY
THREE PHASE
Eat = 0.000 kWh
Erct = 0.000 kVARh
Erit = 0.000 kVARh
Est = 0.000 kVAh
Pt = 167.7 kW
Qt = 30.47 kVAR
St = 170.4 kVA
Meas Time: 00:00:00
Meas
PG-
PG+
Meas
PG-
PG+
ChgP
Meas
PG-
PG+
Example of screen in
single-phase mode
Example of screen in “3-
wire” three-phase mode
Example of screen in “4-
wire” three-phase mode
 
The symbols used are described in Tab. 4. 
For eventual messages displayed see appendix 1
– MESSAGES DISPLAYED.
Following keys are active: 
 
 F2: 
to start / stop immediately a direct energy measurement. The energy 
counters will start increasing proportionally to the active power 
absorbed by the load. 
The results obtained cannot be memorised. 
If the active power is negative the counters will not increase. 
 F1:
(only for 4-wire measurement) to display the following screen. On the 
basis of the settings made as per paragraph 7.1 following screens are 
displayed cyclically: 
total three-phase values, values of phase 1, phase 2 and phase 3
 F3/F4:
to pass to previous/next function respectively
 SAVE:
to save in t
he instrument memory a record of “Smp” type containing
the instantaneous values of voltage and current present at the 
instrument inputs. This function is disabled during a recording 
 ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of
displayed data. All previous functions remain however available. 
When the HOLD function is activated, the word 
HOLD
is displayed.
When this function is enabled it’s not possible to record nor perform 
energy measurements. This function is disabled during a recording or 
an energy measurement 
 MENU:
to enter the MENU mode and change the instrument settings (see 
paragraph 7.1 and 7.2
). It’s not possible to enter the configuration
MENU during a recording or an energy measurement
 START/STOP: to record selected parameters