7.6.2. "METER" mode
By selecting this function the instrument selects automatically the METER mode
corresponding to one of the screens below according to the settings made as per
paragraph 7.1.
27.09.00 17:35:12
27.09.00 17:35:12
27.09.00 17:35:12
SINGLE PHASE
POWER
V1 = 230.0 V
I1 = 145.3 A
P1 = 32.91 kW
Q1 = 5.767 kVAR
S1 = 33.41 kVA
pf1 = 0.99 i
dpf1 = 0.99 i
POWER
THREE WIRE
Pt = 64.19 kW
Qt = 10.99 kVAR
St = 65.12 kVA
pft = 0.99 i
dpft = 1.00 i
POWER
THREE PHASE
Pt = 135.8 kW
Qt = 24.59 kVAR
St = 138.0 kVA
pft = 0.98 i
dpft = 1.00 i
Phseq= 123
WAVE
PG-
PG+
ChgP
WAVE
PG-
PG+
ChgP
WAVE
PG-
PG+
Example of screen in
single-phase mode
Example of screen in “3-
wire” three-phase mode
Example of screen in “4-
wire” three-phase mode
The symbols used are described in Tab. 3.
For eventual messages displayed see appendix 1
– MESSAGES DISPLAYED.
Following keys are active:
F2:
to pass to "WAVE" mode (see paragraph 7.6.3).
F1:
(only for three-phase measurement) to display the previous or the
following screen. On the basis of the settings made as per paragraph
7.1 following screens are displayed cyclically:
Three-phase 3 wires: total three-phase values, Wattmeter phases 1-2 and 2-3 values, peak demand
Three-phase 4 wires: total three-phase values, phase1, phase2 and phase3 values, peak demand
F3/F4:
to pass to previous/next function respectively
SAVE:
to save in the instrument memory a record of “Smp” type and the
instantaneous values of voltage and current present at the instrument
inputs. This function is disabled during a recording
ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of
displayed data. All previous functions remain however available. When
the HOLD function is activated, the word
HOLD
is displayed. When
this function is enabled it’s not possible to record nor perform energy
measurements. This function is disabled during a recording or an
energy measurement
MENU:
to enter the MENU mode and change the instrument settings (see
paragraph 7.1 and 7.2
). It’s not possible to enter the configuration
MENU during a recording or an energy measurement
START/STOP: to record selected parameters