Amprobe – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual
Page 49
AMPROBE
DMIII MULTITEST
EN-47
7.4.
"VOLTAGE" FUNCTION
This function permits to display in real time the RMS value of AC/DC voltage, the peak and
Thd values of the 3 phase voltages, the waveform and the harmonic spectrum of the 3
phase voltages.
7.4.1. Symbols
The VOLTAGE position has three working modes:
METER
WAVE
HARM
These modes will be described in detail in the next paragraphs. The used symbols are
described below:
Symbol
Description
V1, V2, V3
RMS value of voltage (phase 1, phase 2, phase 3 respectively)
V12, V23 or V32,
V31
RMS value of phase to phase voltage
Vpk1, Vpk2, Vpk3,
Vpk12, Vpk32
peak value of voltage (phase 1, phase 2, phase 3 and phase-to-
phase voltage 12 and 32 respectively)
h01
h49
Harmonic 01
Harmonic 49
ThdV
Factor of total harmonic distortion of voltage
freq
Network frequency
Phseq
Phase sequence indicator
"123"
correct
"132"
inverted
"023"
null voltage on black wire
"103"
null voltage on red wire
"120"
null voltage on blue wire
"100"
null voltages on red and blue wires
"020"
null voltages on black and blue wires
"003"
null voltages on black and red wires
Tab. 1: Symbols used in VOLTAGE function