Amprobe – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual
Page 27
AMPROBE
DMIII MULTITEST
EN-25
6.2.4. "MAN" and "TIMER" mode faulty cases
If
the
instrument
detects the External
Power supply adapter
the instrument will
show the message
displayed to the right.
M
05.06.01
-.- -
M
---V 15s
REMOVE POWER
MAN 500V
Disconnect
the
External
Power Supply Adapter
FUNC VNOM
If
the
instrument
detects
a
Voltage
between
the
input
terminals higher than
15V, the instrument
does not perform the
test and displays the
screen to the right for
5 seconds.
M
05.06.01
-.-
-
M
---V 15s
VOLT IN INPUT
MAN 500V
ATTENTION: the test can't be
executed. Check that the circuit is
not energized.
FUNC VNOM
This result can't be saved
If the instrument can't
generate the Nominal
Test Voltage it will
emit a long beep and
displays
a
screen
similar to the screen
to the right.
M
05.06.01
Insulation Resistance
1.17
M
107V 15s
MAN 500V
ATTENTION:
the
test
of
resistance R
ISO
was taken at a
voltage value lower than the
set
rated
voltage.
Low
insulation
case.
This
case
occurs under low insulation
conditions or in the presence of
capacitance on the installation.
FUNC VNOM
Test Duration