Amprobe – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual
Page 27

AMPROBE
DMIII MULTITEST
EN-25
6.2.4. "MAN" and "TIMER" mode faulty cases 
 
 If
the
instrument
detects the External 
Power supply adapter 
the instrument will 
show the message 
displayed to the right. 
M
05.06.01
-.- -
M
---V 15s
REMOVE POWER
 
 MAN 500V
Disconnect
the
External
Power Supply Adapter
FUNC VNOM
 If
the
instrument
detects
a
Voltage
between
the
input
terminals higher than 
15V, the instrument 
does not perform the 
test and displays the 
screen to the right for 
5 seconds. 
 
M
05.06.01
-.-
-
M
---V 15s
VOLT IN INPUT
MAN 500V
ATTENTION: the test can't be 
executed. Check that the circuit is 
not energized.
FUNC VNOM
This result can't be saved
 
 
 If the instrument can't
generate the Nominal 
Test Voltage it will 
emit a long beep and 
displays 
a
screen
similar to the screen 
to the right. 
 
M
05.06.01
Insulation Resistance
1.17
M
107V 15s
MAN 500V
ATTENTION:
the
test
of
resistance R
ISO
was taken at a
voltage value lower than the 
set 
rated
voltage.
Low
insulation
case.
This
case
occurs under low insulation 
conditions or in the presence of 
capacitance on the installation. 
FUNC VNOM
Test Duration
