Technical specifications, Dmiiis, En - 47 – Amprobe DM-111S Current-Data-Logger User Manual
Page 49: Current measurement (using external transducer), Power measurement (cos : 0.5c – 0.5i), Cos measurement
DMIIIS
EN - 47
13. TECHNICAL SPECIFICATIONS
13.1. FEATURES
The accuracy is stated as [% of the reading
number of digits]. It refers to the following
atmospheric conditions: temperature 73°F± 2°F (23°C ± 1°C) with relative humidity < 75%.
13.1.1. Voltage measurement (auto-ranging)
Range
Accuracy
Resolution
Input impedance
15-370V
(0.5%+2digit)
0.2V
300k
(phase-neutral)
600k
(phase-phase)
310-635V
0.4V
13.1.2. Voltage anomalies detection (manual selection of range)
Voltage
Range
Accuracy
Resolution
Input impedance
15-370V
(0.5%+2digit)
0.2V
300k
(phase-neutral)
600k
(phase-phase)
30-635V
0.4V
Time
Accuracy (ref. to 60Hz)
Resolution
8.33ms (½ period of fundamental)
8.33ms (½ period of fundamental)
13.1.3. Current measurement (using external transducer)
Range
Accuracy
Resolution
Input impedance
Protection against
overloads
0.005-0.26V
(0.5%+2digit)
0.0001V
100k
for STD or FlexEXT
8.3k
for FlexINT (1000A)
9.4k
for FlexINT (3000A)
5V
0.26-1V
0.0004V
Minimal Current measurable is equal to 0.5% of Clamp Full Scale
13.1.4. Power measurement (cos
: 0.5c
– 0.5i)
Value
Ranges
Accuracy
Resolution
Active power
0
– 999.9W
1KW
– 999.9KW
1MW
– 999.9MW
(1.0%+2digit)
0.1W
0.1KW
0.1MW
Reactive power
0
– 999.9VAR
1KVAR
– 999.9KVAR
1MVAR
– 999.9MVAR
0.1VAR
0.1KVAR
0.1MVAR
Apparent power
0
– 999.9VA
1KVA
– 999.9KVA
1MVA
– 999.9MVA
0.1VA
0.1KVA
0.1MVA
Active energy
0
– 999.9Wh
1KWh
– 999.9KWh
1MWh
– 999.9MWh
0.1Wh
0.1KWh
0.1MWh
Reactive energy
0
– 999.9VARh
1KVARh
– 999.9KVARh
1MVARh
– 999.9MVARh
0.1VARh
0.1KVARh
0.1MVARh
13.1.5. Cos
measurement
Cos
Resolution
Uncertainty (expressed in
degrees)
0.20
0.01
1.0
0.50
0.7
0.80
0.6