Dmiiis, Recorder config – Amprobe DM-111S Current-Data-Logger User Manual
Page 39

DMIIIS
EN - 37
The chosen configuration is the following
ANALYZER CONFIG:
Frequency:
60Hz
Full scale of the clamps:
1000A
Transforming ratio of voltmetric transformers:
1
Type of electrical equipment:
4 wires
Password:
enabled
RECORDER CONFIG:
Start:
Manual (the recording is started
1 minute after pressing
the START/STOP key)
Stop:
Manual
Integration period:
15min
Recording of harmonics:
ON
Recording of Sag and Surge:
ON
Voltage Reference for Sag and Surge detection:
230V
Upper Limit for Sag and Surge detection:
6%
Lower Limit for Sag and Surge detection:
10%
Selected voltages:
V1, V2, V3
Selected voltage harmonics:
Thd, 01, 03, 05, 07
Selected currents:
I1, I2, I3, IN
Selected current harmonics:
Thd, 01, 03, 05, 07
CO-GENERATION:
OFF
Powers, Pf and cos
selected:
Pt, P1, P2, P3
Qti, Q1i, Q2i, Q3i
Qtc, Q1c, Q2c, Q3c
St, S1, S2, S3
Pft, Pf1, Pf2, Pf3
dpft, dpf1, dpf2, dpf3
Energies:
Eat, Ea1, Ea2, Ea3
Erit, Eri1, Eri2, Eri3
Erct, Erc1, Erc2, Erc3
Est, Es1, Es2, Es3
If the user changed the instrument’s settings can quickly resume the above configuration
using the RESET option (see paragraph 5.5).
By pressing START/STOP the recording of the selected parameters is started according to
the settings made in the MENU (see paragraphs 5.2 and 5.3). The rotary switch position
doesn’t affect the recording setting.
As the default value of the integration periods is set at 15 minutes the instrument will store
data in the temporary memory for 15 minutes. Afterwards the instrument will elaborate the
results saved in the temporary memory and will save the first series of values in the
definitive memory. Therefore, if an integration period of 15 minutes has been set, the
recording will continue for about 15 minutes before producing a series of recorded values.
If the recording is interrupted before the selected integration period has completely
elapsed the data stored in the temporary memory will not be elaborated and the
corresponding series of values won’t be transferred to the definitive memory.