Amprobe DM-111S Current-Data-Logger User Manual
Page 25
DMIIIS
EN - 23
6.1.2. "METER" mode
On rotating the switch to this position the instrument selects automatically the METER
mode corresponding to one of the below screens according to the settings made as per
paragraph 5.2.
27.09.00 17:35:12
27.09.00 17:35:12
27.09.00 17:35:12
SINGLE PH ASE
VOLT AGE
V1 = 230.2 V
Vpk1 = 325.5 V
ThdV = 0.0 %
freq = 60.0 Hz
VOLT AGE
V12 = 384.2 V
V32 = 385.4 V
V31 = 383.7 V
freq = 60.0 Hz
VOLT AGE
V1 = 230.2 V
V2 = 230.5 V
V3 = 230.6 V
V12 = 384.2 V
V23 = 385.4 V
V31 = 383.7 V
freq = 60.0 Hz
Phseq = 123
HARM.
WAVE
HARM.
WAVE
HARM.
WAVE
Example of screen in single-
phase mode
Example of screen in “3 wires”
three-phase mode
Example of screen in “4 wires”
three-phase mode
The symbols used are described in Tab. 1. For eventual messages displayed see
Appendix 1
– MESSAGES DISPLAYED. Following keys are enabled:
F1:
to pass to "HARMONIC" mode (see paragraph 6.1.3).
F2:
to pass to "WAVE" mode (see paragraph 6.1.4).
SAVE:
to save in the instrument memory a record of “Smp” type (see
paragraph 5.4) containing the instantaneous values of voltage and
current present on the instrument inputs. This function is disabled
during a recording.
ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of the
displayed data. All the previous functions remain available. When the
HOLD function is enabled, the word
HOLD
is displayed. When this
function is enabled it’s not possible to record or take an energy
measurement. This function is disabled during a recording or an
energy measurement.
MENU:
to enter in the MENU mode and change the instrument settings (see
paragraph 5.2 and 5.3
). It’s not possible to enter the configuration
MENU during a recording or an energy measurement.
START/STOP: to record selected parameters
according to the instrument’s settings
(see chapter 7).