Emerson Liebert iCOM User Manual
Page 73
Service Menu Parameters
67
COND PUMP-HIGH WATER
CPH
W
Disabled, Enabled
LOSS OF FLOW
LOF
W
Disabled, Enabled
STBY GLYCOL PUMP ON
SGP
W
Disabled, Enabled
STANDBY UNIT ON
STB
W
Disabled, Enabled
HUMIDIFIER PROBLEM
HUP
W
Disabled, Enabled
NO CONNECTION w/Unit1
NOC
W
Disabled, Enabled
UNIT X DISCONNECTED
-
W
Disabled, Enabled
LOSS OF POWER
LOP
W
Disabled, Enabled
TYPE
-
-
-
WORKING HRS EXCEEDED
WHE
W
WRN
SMOKE DETECTED
SMO
W
MSG, WRN, ALM
WATER UNDER FLOOR
WUF
W
MSG, WRN, ALM
COND PUMP-HIGH WATER
CPH
W
MSG, WRN, ALM
LOSS OF FLOW
LOF
W
MSG, WRN, ALM
STBY GLYCOL PUMP ON
SGP
W
MSG, WRN, ALM
STANDBY UNIT ON
STB
W
MSG, WRN, ALM
HUMIDIFIER PROBLEM
HUP
W
MSG, WRN, ALM
NO CONNECTION w/Unit1
NOC
W
WRN
UNIT X DISCONNECTED
-
W
WRN
LOSS OF POWER
LOP
W
MSG, WRN, ALM
Page 6 of 7
PASSWORD
-
W
-
DELAY
-
-
-
CUSTOMER INPUT 1
CI1
W
0 - 9999 sec
CUSTOMER INPUT 2
CI2
W
0 - 9999 sec
CUSTOMER INPUT 3
CI3
W
0 - 9999 sec
CUSTOMER INPUT 4
CI4
W
0 - 9999 sec
CALL SERVICE
CS
W
0 - 9999 sec
HIGH TEMPERATURE
HTD
W
0 - 9999 sec
LOSS OF AIR BLOWER 1
LB1
W
0 - 9999 sec
REHEAT LOCKOUT
RL
W
0 - 9999 sec
HUMIDIFIER LOCKOUT
HL
W
0 - 9999 sec
FC LOCKOUT
FCL
W
0 - 9999 sec
COMPRESSOR(S) LOCKOUT
CL
W
0 - 9999 sec
ENABLE - DISAB
-
-
-
CUSTOMER INPUT 1
CI1
W
Disabled, Enabled
CUSTOMER INPUT 2
CI2
W
Disabled, Enabled
CUSTOMER INPUT 3
CI3
W
Disabled, Enabled
CUSTOMER INPUT 4
CI4
W
Disabled, Enabled
CALL SERVICE
CS
W
Disabled, Enabled
HIGH TEMPERATURE
HTD
W
Disabled, Enabled
LOSS OF AIR BLOWER 1
LB1
W
Disabled, Enabled
Table 28
Set alarms parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
SET
ALARMS