Unit diary—large display only, Table 24 unit diary parameters, Table 24 – Emerson Liebert iCOM User Manual

Page 63: Unit diary parameters

background image

Service Menu Parameters

57

Unit Diary—Large Display Only

Shows all entered program changes and maintenance performed on the unit.

VSD Setpoint

VSD SET

W

0-100%

Page 4 of 5
Password

PASSWORD

W

-

VSD Fanspeed

FANSPEED

W

Auto, Manual, Economy

VSD Setpoint STD

VSD SET

W

HPM: 30-100%

non HPM: 60-100%

VSD Setpoint MIN

VSD MIN

W

HPM: 30-100%

non HPM: 60-100%

VSD Setpoint Dehum

VSD DEH

W

HPM: 30-100%

non HPM: 60-100%

VSD Setpoint No Power

VSD NOP

W

HPM: 30-100%

non HPM: 60-100%

Page 5 of 5
Password

PASSWORD

W

-

SCR Control Type

CTRLTYPE

W

Tight, Standard, Economy

Start Compressor 1 At

CO1 ON

W

-150 to +100%

Stop Compressor 1 At

CO1 OFF

W

-200 to +50%

Compressor 1 Stop Delay

CO1 TD

W

0-30 min

Start Compressor 2 At

CO2 ON

W

-150 to +100%

Stop Compressor 2 At

CO2 OFF

W

-200 to +50%

Compressor 2 Stop Delay

CO2 TD

W

0-30 min

Cycle Time

CYCLET

R

0.2 – 200.0 sec

SCR Factor

SCRFACT

W

1.0 to 10.0

Actual SCR Request

ACT SCR

R

0-100%

Table 24

Unit diary parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 1
Text entered with iST

(iCOM Service Tool)

N/A

R

-

Table 23

Setpoints parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

°C / °F

% RH

SET