Unit diary—large display only, Table 24 unit diary parameters, Table 24 – Emerson Liebert iCOM User Manual
Page 63: Unit diary parameters
Service Menu Parameters
57
Unit Diary—Large Display Only
Shows all entered program changes and maintenance performed on the unit.
VSD Setpoint
VSD SET
W
0-100%
Page 4 of 5
Password
PASSWORD
W
-
VSD Fanspeed
FANSPEED
W
Auto, Manual, Economy
VSD Setpoint STD
VSD SET
W
HPM: 30-100%
non HPM: 60-100%
VSD Setpoint MIN
VSD MIN
W
HPM: 30-100%
non HPM: 60-100%
VSD Setpoint Dehum
VSD DEH
W
HPM: 30-100%
non HPM: 60-100%
VSD Setpoint No Power
VSD NOP
W
HPM: 30-100%
non HPM: 60-100%
Page 5 of 5
Password
PASSWORD
W
-
SCR Control Type
CTRLTYPE
W
Tight, Standard, Economy
Start Compressor 1 At
CO1 ON
W
-150 to +100%
Stop Compressor 1 At
CO1 OFF
W
-200 to +50%
Compressor 1 Stop Delay
CO1 TD
W
0-30 min
Start Compressor 2 At
CO2 ON
W
-150 to +100%
Stop Compressor 2 At
CO2 OFF
W
-200 to +50%
Compressor 2 Stop Delay
CO2 TD
W
0-30 min
Cycle Time
CYCLET
R
0.2 – 200.0 sec
SCR Factor
SCRFACT
W
1.0 to 10.0
Actual SCR Request
ACT SCR
R
0-100%
Table 24
Unit diary parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 1
Text entered with iST
(iCOM Service Tool)
N/A
R
-
Table 23
Setpoints parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
°C / °F
% RH
SET