Service Menu Parameters
66
ENABLE - DISAB
-
-
-
COMP 1 OVERLOAD
OL1
W
Disabled, Enabled
COMP 2 OVERLOAD
OL2
W
Disabled, Enabled
COMP 1 HIGH PRESSURE
HP1
W
Disabled, Enabled
COMP 2 HIGH PRESSURE
HP2
W
Disabled, Enabled
COMP 1 LOW PRESSURE
LP1
W
Disabled, Enabled
COMP 2 LOW PRESSURE
LP2
W
Disabled, Enabled
COMP 1 PUMPDOWN FAIL
PD1
W
Disabled, Enabled
COMP 2 PUMPDOWN FAIL
PD2
W
Disabled, Enabled
DIG SCROLL1 HIGH TEMP
HT1
W
Disabled, Enabled
DIG SCROLL2 HIGH TEMP
HT2
W
Disabled, Enabled
EL HEAT HIGH TEMP
EHO
W
Disabled, Enabled
TYPE
-
-
-
COMP 1 OVERLOAD
OL1
W
MSG, WRN, ALM
COMP 2 OVERLOAD
OL2
W
MSG, WRN, ALM
COMP 1 HIGH PRESSURE
HP1
W
MSG, WRN, ALM
COMP 2 HIGH PRESSURE
HP2
W
MSG, WRN, ALM
COMP 1 LOW PRESSURE
LP1
W
MSG, WRN, ALM
COMP 2 LOW PRESSURE
LP2
W
MSG, WRN, ALM
COMP 1 PUMPDOWN FAIL
PD1
W
MSG, WRN, ALM
COMP 2 PUMPDOWN FAIL
PD2
W
MSG, WRN, ALM
DIG SCROLL1 HIGH TEMP
HT1
W
MSG, WRN, ALM
DIG SCROLL2 HIGH TEMP
HT2
W
MSG, WRN, ALM
EL HEAT HIGH TEMP
EHO
W
MSG, WRN, ALM
Page 5 of 7
PASSWORD
-
W
-
DELAY
-
-
-
WORKING HRS EXCEEDED
WHE
W
0 - 9999 sec
SMOKE DETECTED
SMO
W
0 - 9999 sec
WATER UNDER FLOOR
WUF
W
0 - 9999 sec
COND PUMP-HIGH WATER
CPH
W
0 - 9999 sec
LOSS OF FLOW
LOF
W
0 - 9999 sec
STBY GLYCOL PUMP ON
SGP
W
0 - 9999 sec
STANDBY UNIT ON
STB
W
0 - 9999 sec
HUMIDIFIER PROBLEM
HUP
W
0 - 9999 sec
NO CONNECTION w/Unit1
NOC
W
internal
UNIT X DISCONNECTED
-
W
internal
LOSS OF POWER
LOP
W
internal
ENABLE - DISAB
-
-
-
WORKING HRS EXCEEDED
WHE
W
Disabled, Enabled
SMOKE DETECTED
SMO
W
Disabled, Enabled
WATER UNDER FLOOR
WUF
W
Disabled, Enabled
Table 28
Set alarms parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
SET
ALARMS