beautypg.com

Glycool™ cooling—free-cooling, Dual cooling source, 5 temperature control—reheat – Emerson Liebert iCOM User Manual

Page 29: Table 4 reheat configuration types, Temperature control—reheat, Three-stage electric, hot gas and hot water reheat, Table 4, Reheat configuration types

background image

Operation

23

GLYCOOL

Cooling—Free-Cooling

When GLYCOOL cooling is available, the temperature control will calculate a total cooling require-

ment of 200% rather than 100%. Assuming that full GLYCOOL capacity is available, the GLYCOOL

valve opens proportionally as the requirement for cooling rises from 0 to 100%. If more than 100%

cooling is required, then the compressors are activated at 150% and 200% respectively (133%, 163%,

180% and 200% for a four-step system). If full GLYCOOL capacity is not available, then the GLY-

COOL valve will be opened proportionally over a cooling requirement band equal to the available

GLYCOOL capacity. The compressors would be activated when the GLYCOOL capacity is exceeded.
For example, if the GLYCOOL capacity is 60%, then the GLYCOOL valve would be full open at 60%

cooling requirement and the compressors would activate at 110% and 160% cooling requirement. In

order to reduce compressor cycling and prevent hunting, GLYCOOL capacity first becomes available

when the entering glycol temperature is at least 8°F (4.4°C) (22% capacity) below the return air tem-

perature, or 3°F (1.7°C) below the return air temperature for two hours. GLYCOOL capacity is 100%

when the glycol temperature is 25°F (13.9°C) below the return air temperature. The system will con-

tinue to operate in Econ-O-Cool mode as necessary as long as the entering glycol temperature

remains at least 3°F (1.7°C) (0% capacity) below the return air temperature. If GLYCOOL is not

available, the temperature control will operate the compressors in the same manner as a two-step or

four-step system without GLYCOOL.

Dual Cooling Source

If dual cooling is available, the sensible cooling system operates in the same manner as a GLYCOOL

system, except that it is assumed that 100% chilled water capacity is available any time the chilled

water temperature is 3°F (1.7°C) below the return air temperature.

3.5

Temperature Control—Reheat

If the room air temperature becomes too cold, the control will call for heating. Heating mode is con-

trolled by the Temperature Proportional Band, explained in 3.3.1 - Temperature Proportional

Band.

3.5.1 Three-Stage Electric, Hot Gas and Hot Water Reheat

The Reheat Proportional Band is divided into three equal parts, each representing one reheat stage.

As the Temperature Proportional Band increases the call for heating from 0% to -100%, stages 1

through 3 are switched On, as shown in Figure 19. Your unit will have one of the nine reheat config-

uration types shown in Table 4.
Table 4

Reheat configuration types

Type

A

B

C

D

E

F

G

H

I

Stage 1 Electric 1 Electric 1 Electric 1 Hot Gas

Hot Gas

Hot Gas

Hot Water

Hot Water

Hot Water

Stage 2

-

Electric 2 Electric 2

-

Electric 1 Electric 1

-

Electric 1

Electric 1

Stage 3

-

-

Electric 3

-

-

Electric 2

-

-

Electric 2

NOTE
1. Hot gas / hot water are not influenced by the setting of electric reheat during

dehumidification.

2. Hot gas output will be set only if the selected compressor is in operation.