Figure 19 Three-stage heating

0%

Heating

65

70

Heat 3

On

½ Dead-

band

66

67

68

69

Heat 2

On

Heat 1

On

Heat 3

Off

Heat 2

Off

Heat 1

Off

-100 %

Heating

½ Proportional Band

Decreasing Temperature

Temp Setpoint: 70°F
Proportional Band: 8°F
Deadband: 2°F