beautypg.com

0 service menu parameters, Table 23 setpoints parameters, Ervice – Emerson Liebert iCOM User Manual

Page 62: Arameters, Table 23, Setpoints parameters

background image

Service Menu Parameters

56

8.0

S

ERVICE

M

ENU

P

ARAMETERS

Service menus allow customized settings for site operations. The password for service menu parame-

ters is 5010.
The iCOM control firmware is being updated constantly. As a result, the Service menu parameter

tables shown in this manual may be slightly different than what is shown on your cooling unit's dis-

play. Please check

www.liebert.com

for the latest iCOM User manual updates.

Table 23

Setpoints parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 5
Password

PASSWORD

W

-

Temperature Setpoint

TEMP SET

W

41-104°F (5-40°C)

Control Type

CTRL TYP

W

Proportional, PI, PID, Intelligent

Temperature Proportional Band

TEMP PB

W

2-54°F (1-30°C) autoset

Temperature Integration Time

TEMP INT

W

0-15 min, autoset

Temperature Derivative Time

TEMP DER

W

0-900 sec

AutoSet Enable

AUTOSET

W

No, Yes

Temperature DeadBand

TEMP DB

W

0-36°F (0-20°C)

Second Setpoint

2ND SETP

W

41-104°F (5-40°C)

Backup Temperature Setpoint

BACK TSP

W

41-104°F (5-40°C)

Page 2 of 5
Password

PASSWORD

W

-

Humidity Setpoint

HUM SET

W

20-80%

Humidity Control Type

HUM CTRL

W

Relative, Compensated, Predictive

Humidity Proportional Band

HUM PB

W

1-20%

Humidity Integration Time

HUM INT

W

0-15 min

Humidity Deadband

HUM DB

W

0-50%

Dehum/Heat Low Limit 1

LO LIM 1

W

-9.9°F to -2.0°F

Dehum/Heat Low Limit 2

LO LIM 2

W

-9.9°F to -2.0°F

internal variable Low Limit 1 reset

-10.0°F / -2.0°F

-5.5K / -1.1K

internal variable Low Limit 1 reset

-10.0°F / -2.0°F

-5.5K / -1.1K

Page 3 of 5
Password

PASSWORD

W

-

Supply Limit

SUP LIM

W

Enabled, Disabled

Supply Limit Temp Value

SUP TEMP

W

41-77°F (5-25°C)

DT between Room / FC Type

FC TYPE

W

No, Contact, Value

DT between Room Air/ FC Fluid

FC DT

W

0-36°F (-18 - 2 °C)

Minimum CW Temp

MIN CW

W

No, Yes

Minimum CW Temp Value

MIN CW

W

32-68°F (0-20°C)

VSD Fanspeed

FANSPEED

W

Auto / Manual

°C / °F

% RH

SET