Table 8 – Emerson Liebert iCOM User Manual
Page 41
Operation
35
Table 8
Possible event settings—some events not available in all units
Event
Internal Delay
(Before Action Occurs)
Default Delay / Selectable
(Before Action Occurs)
Type
(default)
MAIN FAN OVERLOAD
2 seconds
5 seconds / 0 – 9999 *
ALM
LOSS OF AIRFLOW
3 seconds
3 seconds / 0 – 9999 *
ALM
CLOGGED FILTERS
2 seconds
2 seconds / 0 – 9999 *
WRN
HIGH ROOM TEMP
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
LOW ROOM TEMP
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
HIGH ROOM HUM
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
LOW ROOM HUM
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
HIGH TEMP SENSOR A
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
LOW TEMP SENSOR A
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
HIGH HUM SENSOR A
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
LOW HUM SENSOR A
1 Min After Fan On
30 seconds / 0 – 9999
Fixed to WRN
COMP 1 OVERLOAD
Internal Calc.
no
ALM
COMP 2 OVERLOAD
Internal Calc.
no
ALM
COMP 1 HIGH PRESSURE
Internal Calc.
no
ALM
COMP 2 HIGH PRESSURE
Internal Calc.
no
ALM
COMP 1 LOW PRESSURE
Internal Calc.
no
ALM
COMP 2 LOW PRESSURE
Internal Calc.
no
ALM
COMP 1 PUMPDOWN FAIL
Internal Calc.
no
ALM
COMP 2 PUMPDOWN FAIL
Internal Calc.
no
ALM
DIG SCROLL1 HIGH TEMP
Internal Calc.
no
ALM
DIG SCROLL2 HIGH TEMP
Internal Calc.
no
ALM
EL HEAT HIGH TEMP
5 Sec
0 sec / 0 – 9999
WRN
WORKING HRS EXCEEDED
0 Sec
0 sec / 0 – 9999
Fixed to WRN
SMOKE DETECTED
2 Sec
2 sec / 0 – 9999 *
ALM
WATER UNDER FLOOR
2 Sec
2 sec / 0 – 9999 *
ALM
COND PUMP-HIGH WATER
2 Sec
2 sec / 0 – 9999 *
ALM
LOSS OF FLOW
5 Sec
Reset Delay: 10 Sec
2 sec / 0 – 9999 *
ALM
STBY GLYCOL PUMP ON
2 Sec
2 sec / 0 – 9999 *
ALM
STANDBY UNIT ON
2 Sec
2 sec / 0 – 9999 *
ALM
HUMIDIFIER PROBLEM
2 Sec
2 sec / 0 – 9999 *
ALM
NO CONNECTION w/Unit1
Internal Calc.
-
WRN
UNIT X DISCONNECTED
Internal Calc.
-
WRN
LOSS OF POWER
0 Sec
No
ALM
CUSTOMER INPUT 1
2 Sec
2 sec / 0 – 9999 *
ALM
CUSTOMER INPUT 2
2 Sec
2 sec / 0 – 9999 *
ALM
CUSTOMER INPUT 3
2 Sec
2 sec / 0 – 9999 *
ALM
CUSTOMER INPUT 4
2 Sec
2 sec / 0 – 9999 *
ALM
CALL SERVICE
2 Sec
2 sec / 0 – 9999 *
MSG
HIGH TEMPERATURE
2 Sec
2 sec / 0 – 9999 *
MSG
LOSS OF AIR BLOWER 1
2 Sec
2 sec / 0 – 9999 *
ALM
REHEAT LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
HUMIDIFIER LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
FC LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
COMPRESSOR(S) LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
COMP 1 SHORT CYCLE
0 Sec
0 - 9999
MSG
COMP 2 SHORT CYCLE
0 Sec
0 - 9999
MSG