beautypg.com

2 dehumidification, Dehumidification low limit, Dehumidification compressor quantity – Emerson Liebert iCOM User Manual

Page 35: Table 6 dehumidification with comp settings, Dehumidification, Table 6, Dehumidification with comp settings

background image

Operation

29

3.6.2 Dehumidification

The Dehumidification Enable parameter (Service Menu, Options Setup) allows for enabling/disabling

the dehumidification function.
A call for dehumidification is calculated in the same way as a cooling request. The components

(valves, compressors) will follow this dehumidification request as soon as it is higher than the request

for cooling.

Dehumidification Low Limit

Low Limit 1 and Low Limit 2 are used to avoid overcooling a room during dehumidification. When a

low limit is reached, a compressor or the liquid cooling source that is used for dehumidification is dis-

abled. It is re-enabled when the return air temperature rises. The Low Limit 1 and 2 settings are in

the Service menu under Setpoints.
Low Limit 1: Low Limit 1 will disable one of two compressors for dehumidification. If only one com-

pressor is set for dehumidification, or if the dehumidification source is chilled water, this limit will

not be visible and will be inactive.
Low Limit 2: Low Limit 2 will disable both compressors for dehumidification. This limit will also

stop dehumidification in single compressor units and in chilled water units.
The limits become active when the return air temperature drops below a temperature value equal to

the sum of the temperature setpoint plus the value set on Low Limit 1 and 2 (the Low Limit settings

are negative values).
A dehumidification source is deactivated if the return air temperature drops below the Deactivation

Temperature, as in this example:

Dehumidification Compressor Quantity

Under Factory Settings in the Advanced menu there is an item called Dehumidification With Comp.

This item will be set to either 1, 2, 1 or 2, or BOTH. This setting determines which compressors are

used for dehumidification. It also determines if Low Limit 1 will be available and impacts how the

reheats will operate during dehumidification. The Dehumidification With Comp field is set when the

cooling unit is built and should not be adjusted without consulting the factory first. Table 6 outlines

which Low Limit settings will be available, based on the Dehumidification With Comp selection.

Low Limit 1 & 2 will be available only on cooling units with two compressors when Dehumidification

With Comp is set to BOTH (see WARNING on page 30).

Temperature Setpoint:

70°F

Low Limit Value:

-7°F

Deactivation Temperature:

62°F

NOTE
If a cooling unit is equipped with SCR reheat and the SCR Control Type parameter is set to

Tight mode, then Low Limit 2 will be ignored, see 3.5 - Temperature Control—Reheat.

Table 6

Dehumidification With Comp settings

Available to Set Value

Dehumidification With Comp Setting

Default Setting On

Low Limit 2 only

[blank] (units without compressors)

All Chilled Water Units

1 (Compressor 1 dehumidifies only)

Liebert Challenger 3000

, Liebert DS

,

Liebert Deluxe System/3

2 (Compressor 2 dehumidifies only)

1 or 2 (Compressor 1 and 2 alternate)

Low Limit 1 & 2

Both (both compressors dehumidify)