Precision Digital PD6400 User Manual
Page 66
Model PD6400 High Voltage & Current Meter
Instruction Manual
66
Display
Parameter
Action/Setting
No pts
Number of
points
Set the number of linearization points
(default: 2)
nmath
Math
Enter the setup menu for channel P math
function
nmulti
Multiplication
Channel P = ((A*V)+C)*F
Const
Constant
Constant used in channel P math
adder
Adder
Addition constant used in channel P math
calculation (C)
factor
Factor
Multiplication constant used in channel P
math calculation (F)
CutofF
Cutoff
Set low-flow cutoff
Ch-A
Channel A
Set low-flow cutoff for Channel A
Ch-v
Channel V
Set low-flow cutoff for Channel V
AoutPr
Analog output
programming
Program analog output parameters
AOut 1*
Analog output 1
Program analog output 1 (*1-3)
parameters
Source
Source
Select source for the 4-20 mA output
break
Loop break
Set relay condition if loop break detected
O-rang
Overrange
Program mA output for display overrange
u-rang
Underrange
Program mA output for display underrange
nmAx
Maximum
Program maximum mA output allowed
nmin
Minimum
Program minimum mA output allowed
Calib
Calibrate
Calibrate 4-20 mA output (internal
reference source used for scaling the
output)
4 nmA
4 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
20 nmA
20 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
User
User I/O
Assign function keys and digital I/O
F1*
F1* function key
Assign F1 function key (*F1/F2/F3)